Amico medical gas design guide1/12/2024 The unit shall be compact, measuring 19" high x 17" wide x 9" deep (483 mm x 432 mm x 229 mm). The manifold has an intermediate and line relief valve that is internally connected to a common vent port, terminating into a 1/2" (13 mm) FNPT pipe. The manifold consists of two bank regulators (dome bias) used to reduce the cylinder pressure to the two line regulators which in turn controls the final line pressure. The control panel includes a line gauge, two bank gauges and incorporates six LED s: two green for Bank in Use, two yellow for Bank Ready and two red for Bank Empty on the front of the cabinet. After the switchover, the Reserve Bank shall then become the Bank in Use and the Bank in Use shall become the Reserve Bank. 1 Automatic Medical Gas Manifold Dome Loaded Manifold NFPA General Specifications: The Manifold shall be a fully automatic type and shall switch from Bank in Use to Reserve Bank without fluctuation in the final line pressure.